A reliable variable speed drive installation begins before power is applied. Engineers and system integrators must verify supply compatibility, provide suitable mounting and cooling, separate power and control wiring, and establish safe procedures for servicing. These decisions affect both equipment protection and the quality of the installation, so they should be treated as part of the system design rather than as final assembly details.
The Altivar 71 installation guidance applies to drives used with synchronous and asynchronous motors across several voltage and power ranges. The principles below offer a practical framework for planning and installing a drive, while exact ratings, clearances and connection details must always be checked against the specific drive model and its current documentation.
Plan the installation before wiring
Start by checking the drive’s nameplate against the project requirements. Confirm that the available line voltage falls within the drive’s rated supply range and that the motor connections correspond to the intended voltage. Also inspect the delivered equipment and packaging. A drive that appears damaged should not be installed or operated.
Complete mounting and wiring work with power off. Before commissioning, verify the power, motor, control and speed-reference connections. In particular, do not apply incoming line voltage to the drive’s motor output terminals. Confirm power connections before energizing, and coordinate overcurrent protection with the drive’s nameplate and applicable electrical requirements.
Variable speed drive installation: safety first
Drive installation, adjustment, repair and maintenance require qualified personnel. Internal components and circuit boards may operate at line voltage, and the DC bus can retain hazardous energy after the supply is disconnected. Do not rely on indicator lights alone to determine that the bus is safe.
Before servicing, disconnect all power sources, including any external control supply. Lock the disconnect in the open position and label it to prevent reconnection. Allow the specified discharge time, then use a properly rated voltage-sensing device to verify the DC bus voltage according to the drive’s procedure. Covers should be installed before power is applied or the drive is operated.
Prevent unexpected starts during setup. Check that the Power Removal input and run-command inputs are in their inactive states before turning on the drive or leaving configuration menus. Where personnel safety depends on preventing unintended operation, the safety function must be implemented using the required safety architecture and connection diagrams; it is not a substitute for following the relevant programming and safety instructions.
Mounting, airflow and enclosure temperature
Mount the drive vertically within the permitted orientation and keep it away from heat sources. Leave the clearances required for air to move through the unit, typically from bottom to top, and maintain the specified front access space. Mounting arrangement matters: side-by-side installation or removing a protective cover can change the permitted spacing and the enclosure’s protection level.
For installation inside a cabinet, account for the heat the drive dissipates at its rated operating conditions. Provide ventilation openings or filtered forced ventilation as required, and ensure airflow is sufficient for the selected drive. In dusty, humid or corrosive environments, a suitably protected enclosure may be necessary. Internal air circulation can also help avoid localized hot spots.
Temperature, switching frequency and mounting configuration influence the current available from the drive. If operating conditions exceed the conditions associated with the nominal rating, apply the specified derating. Do not assume that a drive’s nameplate current is available under every cabinet or ambient condition.
Grounding and EMC-conscious wiring
Connect the drive to protective ground using the designated grounding point, and establish a sound grounding arrangement for the installation. The guidance calls for a protective conductor sized for the applicable leakage-current requirements and advises against connecting multiple drives to ground in a loop or series. Follow local electrical standards and the drive’s instructions when selecting conductors and protective devices.
Route motor and power cables separately from low-level circuits such as sensor, PLC and measurement wiring. Keep control circuits away from power circuits; shielded twisted-pair cable is recommended for control and speed-reference signals, with the shield grounded at both ends as specified. If power and control routes must cross, cross them at right angles. Avoid placing motor, supply and control cables together in the same conduit.
Use the specified EMC plates and clamps where applicable, and pay attention to motor-cable length and cable type. Depending on the installation and cable run, output filters may be needed to address leakage-current issues. Do not install surge arresters or power-factor-correction capacitors on the drive output. For braking resistors, use an approved compatible component and wire its thermal protection so a fault disconnects the drive supply as required by the resistor instructions.
Commission methodically
A disciplined startup sequence reduces the chance of avoidable equipment damage or unexpected motion. Before energizing, check:
- The drive model and supply voltage match the application.
- The drive is securely mounted with adequate cooling clearance.
- Protective grounding and overcurrent protection are correctly installed.
- Power, motor and control wiring are connected to the intended terminals.
- Run commands and the Power Removal input are in the required inactive state.
- Option cards and terminal connections are seated and secured correctly.
After these installation checks, use the programming documentation to configure the drive for the application. If a drive has been stored or left unpowered for a prolonged period, follow the manufacturer’s capacitor-maintenance guidance before returning it to service.
Conclusion
Good variable speed drive installation practice combines electrical safety, correct grounding, thermal planning and careful cable routing. Verifying ratings and wiring before power-up, respecting DC-bus discharge procedures, and designing the enclosure around airflow and operating conditions help create a sound basis for commissioning. Always use the documentation for the exact drive and options installed, and have qualified personnel perform electrical work and maintenance.