An industrial softstarter can help control motor starting and stopping in applications that operate at full speed. By gradually increasing motor voltage during startup, it can limit inrush current and reduce the mechanical shock associated with abrupt starts. The right choice depends on motor and load requirements, the electrical network, the starting duty and the application features needed—not simply the motor’s rated current.
Why motor starting and stopping need control
Direct-on-line (DOL) starting applies full voltage immediately. It is simple and commonly used, but produces high starting current and torque. This can be suitable for stable electrical networks and mechanically robust, well-dimensioned shaft systems; in other applications, the resulting electrical and mechanical stresses can be undesirable.
Star-delta starting reduces starting current to about one-third of DOL, but also lowers starting torque to about 25 percent. Its settings are not adjustable, and switching from star to delta can create current peaks. A softstarter offers adjustable starting and stopping behavior, making it a practical middle ground for many full-speed motor applications.
A variable speed drive (VSD) can also provide soft starting and stopping, but its primary purpose is to control motor speed. Where a motor runs at full speed and the requirement is limited to managing starts and stops, a softstarter may be a more appropriate solution than using a VSD solely for that purpose. If the process requires speed control, that requirement should inform the drive choice.
Industrial softstarter selection: match range to need
Softstarter ranges differ in current capacity, control, protection and application functions. The catalog describes three ranges, each intended for a different combination of installation constraints and operating needs:
- PSR, compact range: Rated operational current is 3–105 A, with operational voltage of 208–600 V AC. It uses two-phase control, voltage ramps for starting and stopping, a built-in bypass and a straightforward setup using three potentiometers. It can be combined with a manual motor starter to create a compact solution with overload and short-circuit protection.
- PSE, efficient range: Rated operational current is 18–370 A, with operational voltage of 208–600 V AC. Designed with pump operation in mind, it adds torque control for starting and stopping, current limit, kick-start and electronic motor protection. Its built-in bypass and compact design support panel integration.
- PSTX, advanced range: Rated operational current is 30–1,250 A, or up to 2,160 A for inside-delta connection, with operational voltage of 208–690 V AC. It supports both in-line and inside-delta connections and includes a broader set of functions, including a graphical display, built-in Modbus RTU, analog output and extensive motor protection.
These ranges are not interchangeable feature-for-feature. Confirm that a candidate unit supports the required motor current and voltage, connection arrangement, start duty, controls and protections. Selection should also account for how frequently the motor starts and the application’s load conditions. The catalog’s stated start-capacity and starts-per-hour conditions vary by range; consult the applicable technical data and selection guidance rather than assuming a rating covers every duty.
Choose application features for operational problems
Pumps: manage stopping, clogging and dry running
When a pump stops abruptly, pressure changes can contribute to water hammer and wear on pipes and valves. Torque-controlled stopping is designed to manage the stopping process and help address this problem. Some softstarter ranges also offer pump-cleaning functions that reverse flow and restart with a kick-start to help clear clogging. Underload protection can stop a motor when a pump is running dry, limiting additional wear. Check the selected model’s feature set before specifying these functions.
Fans: tune starts and stops to inertia
Fans can have high inertia, making startup demanding. A gradual voltage ramp and adjustable settings allow the start to be matched to the load, from unloaded to fully loaded conditions. Where a fan needs to stop quickly, a dynamic braking function may reduce stopping time. A standstill brake can help prevent an idle fan from rotating due to wind or airflow from another fan, where that function is available.
Conveyors and compressors: protect the process
On a conveyor, overload protection can stop the motor if excessive material creates an overload condition. Slow-speed forward and reverse jog can help position a belt before restarting, while limp mode on supported equipment can allow continued operation with one thyristor shorted. For compressors, current limiting can help manage starting current in a weaker network. Phase-reversal protection can prevent a motor from starting in the wrong direction, which is important where rotation direction affects compressor operation.
Plan the complete motor starting solution
A softstarter is one part of a motor-control system. The installation may also require short-circuit protection, overload protection, a line contactor, control devices, a power supply, PLC connections and terminal blocks. The appropriate configuration depends on the application and the required protection coordination. For example, the catalog notes that specific external protection arrangements are needed for ATEX motor applications; the softstarter must be outside the Ex area, and an approved overload relay and line contactor are required under the stated conditions. Marine installations also require attention to network and grounding considerations.
Panel design matters as well. Built-in bypass can reduce heat generation in operation and save panel space, while compact dimensions and built-in functions can simplify installation. However, engineers must still check mounting clearances, ambient temperature, altitude derating, wiring and protection requirements against the selected model’s documentation.
Conclusion: select for the motor, load and process
Softstarter selection starts with the motor and operating duty, then considers what the process needs from starting, stopping and protection. PSR, PSE and PSTX cover different capacity and feature requirements, from compact installations to advanced application control. Matching the range and configuration to the actual load can help limit starting stress, support equipment reliability and avoid specifying capabilities the application does not need. Verify ratings, protection coordination and installation conditions using the technical data for the exact softstarter model.