Non-contact safety switches provide a way to monitor movable machine guards without a mechanical contact between the switch and actuator. In the CES-A-C5 system, a coded actuator is paired with a safety switch that combines a read head and evaluation unit. When the guard closes and the assigned actuator is detected, the system can enable its safety outputs; when the guard opens, those outputs switch off. Safe operation depends not only on the device, but also on correct selection, installation, wiring and validation within the machine’s safety-related control system.

How coded non-contact safety switches work

The system has three main elements: a coded actuator mounted on the movable guard, a safety switch mounted on the fixed part of the guard, and an evaluation unit integrated into the switch housing. As the guard closes, the actuator approaches the read head. The read head supplies power to the actuator inductively and reads its electronic code.

The evaluation unit compares the received code with the code stored during teach-in. If they match, the two semiconductor safety outputs, LA and LB, switch on. The separate door-monitoring output, OUT, also indicates that an actuator has been detected, but it is not a safety output. Opening the guard removes the actuator from the operating distance, causing the safety outputs to switch off and the monitoring output to go low.

The CES-A-C5 family uses dynamic actuator polling and redundant, self-monitoring safety electronics. The manual identifies the CES-A-C5E-01 as Category 3, PL e, and the CES-A-C5H-01 as Category 4, PL e, according to EN ISO 13849-1. These classifications apply to the specified devices and conditions; they do not establish the performance level of an entire machine by themselves. The complete safety-related control system must be designed and validated for its application.

Start with risk assessment and correct component selection

Before using an interlocking device, assess the machine’s risks and determine the required safety functions. The manual points to machinery safety and functional safety standards for risk assessment, safety-related control system design, interlocking devices and machine electrical equipment. The selected safety switch must be used with a compatible actuator listed for that device. Substituting an unapproved actuator can compromise safe function.

Integration is the responsibility of the machine builder or system integrator. Consider how opening a guard stops hazardous movement, how unexpected restart is prevented, and how the safety switch interacts with the safety PLC or other evaluation equipment. The overall system requires validation; fitting a safety-rated switch alone is not sufficient.

Installation: alignment, distance and tamper resistance

Mount the switch and actuator so that the designated actuator is the one that triggers operation. Secure the actuator to the movable guard, using the supplied safety screws where specified, and arrange the installation so it cannot be easily removed or tampered with. Do not use the safety switch as a mechanical end stop. Provide a separate stop to limit guard movement.

Observe the operating distances for the particular actuator and mounting arrangement. The manual gives different assured switch-on and switch-off distances for different actuator models; flush mounting and surrounding materials can also affect switching distance. Ensure the guard is far enough from the read head when open to exclude the hazard, and position components so that the operating distance is not inadvertently entered from a side lobe. Where multiple switches are installed, maintain the specified minimum separation of 80 mm to avoid mutual interference.

The read head’s active face can be adjusted to suit the approach direction. During adjustment, take care not to trap or damage cables. Follow the stated mounting torque limits, which vary for some materials, and keep components accessible for inspection and replacement.

Wire both safety outputs into the safety circuit

Both LA and LB must be evaluated by the connected safety control system. Using only one safety output reduces the achievable category. OUT is a status signal, not a substitute safety channel. For the stated Category 3 or Category 4 design, downstream contactors must also be monitored as required by the application.

Check the electrical interface before connecting the device. The outputs are positive-switching, so connected inputs must be suitable for that signal type. The manual also warns that the device is not suitable for safety relays that perform short-circuit monitoring using different potentials of 0 V and 24 V. A short circuit between LA and LB must be detected through external pulsing or excluded through protected cable routing. Route safety signal wiring away from power circuits, and apply appropriate suppression to inductive loads.

Use the specified supply and protective measures, including suitable isolation and overcurrent protection. Cable length and switching current can contribute to voltage drop, so check the expected load and wiring against the device’s technical data. Electrical work should be carried out by authorized personnel with the device and wiring isolated.

Teach-in, commissioning and fault checks

An actuator must be taught to the evaluation unit before the system can operate as a functional pair. During teach-in, the safety outputs and OUT remain low, leaving the system in its safe state. The unit can operate only with the last actuator taught, and the same actuator cannot be taught repeatedly to the same unit. Teach-in is limited to eight operations.

For a new actuator, follow the manufacturer’s sequence: apply operating voltage, bring the actuator within the specified distance, allow the teach-in process to complete, then interrupt power for at least 10 seconds to activate the stored code. The manual describes a 60-second teach-in period. If the process is interrupted or power is removed during teach-in, it is invalid. Confirm the system status indicators and perform a functional check after the procedure.

Commissioning should verify that the machine does not start automatically when the guard closes, and that it stops and cannot restart while the guard is open. Conduct the check with no one in the danger area, and repeat it for every monitored guard. Recheck the safety function after setup work, component replacement, an extended period without use and any fault.

Ongoing inspection and practical implications

Include the safety guard in the machine maintenance schedule. Check switching function, secure mounting, connections, cleanliness, plug sealing, cable connections and switch-off distance. If a safety component is damaged, replace the component rather than attempting to replace individual internal parts. The manual states that repairs are to be performed by the manufacturer and that no routine servicing is required.

For engineers and plant teams, the key takeaway is that coded non-contact safety switches are one part of a validated machine safety function. Correct actuator pairing, mechanical installation, two-channel output evaluation, suitable downstream monitoring and documented functional checks all contribute to reliable guard interlocking. Treating these requirements as part of system design and maintenance—not simply device installation—helps ensure the guard’s safety function is preserved throughout operation.