Offshore wind farm configurations determine how turbine-generated electricity is collected, converted and transmitted to shore. For engineers and project decision-makers, the choice affects more than the electrical path: it also shapes the amount of equipment needed offshore, the transmission approach and the demands placed on wind turbine components. Four broad architectures are used or proposed: parallel AC collection with HVAC transmission, parallel AC collection with HVDC transmission, parallel DC collection with HVDC transmission, and series DC connection with HVDC transmission.

How an offshore wind farm delivers power

A wind farm’s electrical system can be considered in two parts: the generation and collection system, and the transmission link to the onshore grid. Variable-speed wind energy conversion systems use power converters to adjust generator speed and capture power as wind conditions change. This approach also reduces mechanical stress compared with fixed-speed systems.

In a common arrangement, turbine output is stepped up by a transformer to a medium-voltage collection level, such as 33 kV. Power is then gathered offshore and passed through additional equipment before transmission to shore. Depending on the architecture, that equipment can include transformers, converters and reactive power compensation. Housing these components on an offshore platform makes the platform’s footprint and weight significant design considerations.

HVAC is generally the simpler, more economical transmission option when the offshore-to-onshore distance is below about 50 km. For longer distances, HVDC is commonly used. The choice reflects, in part, the electrical characteristics of submarine AC cables and the equipment required to convert between AC and DC.

Four offshore wind farm configurations

1. Parallel AC collection with HVAC transmission

In this arrangement, each turbine’s output is transformed to a medium-voltage AC level. Turbine outputs connect in parallel to form the collection network, and offshore transformers raise the voltage for HVAC transmission to shore.

Its main advantage is simplicity for shorter transmission distances. As AC cable distance and voltage increase, however, cable capacitance produces reactive current. This reduces the cable’s capacity to carry active power, and reactive power compensation is normally required at both ends. HVAC also cannot directly connect AC networks operating at different frequencies, and faults in the cable can affect the connected system.

2. Parallel AC collection with HVDC transmission

Here, turbines are still connected through a parallel AC collection system, but offshore conversion equipment changes the power to DC for transmission. Onshore equipment converts it back to AC for connection to the grid. This arrangement is used for large-capacity wind farms located far from shore.

Voltage source converters (VSCs) offer independent control of active and reactive power and fast dynamic response. Modular multilevel converters (MMCs) are a prominent VSC approach for HVDC applications; their modular design supports near-sinusoidal output waveforms with low switching frequency. The trade-off is the need for substantial offshore equipment, including transformers and converters, which contributes to the platform’s size, weight and cost.

Line-commutated converter (LCC) systems are another HVDC option. They require a sufficiently strong AC voltage source for thyristor commutation and need reactive power support. They also do not provide independent control of active and reactive power. Their large footprint makes them less suitable for offshore platforms.

3. Parallel DC collection with HVDC transmission

This proposed architecture converts turbine output to DC, then uses DC/DC conversion to raise it to a medium-voltage DC collection level. The turbine-side DC outputs connect in parallel, and a centralized converter raises the voltage again for HVDC transmission to shore. The DC/DC conversion stages typically include DC/AC conversion, a medium- or high-frequency transformer, and AC/DC conversion.

Compared with parallel AC collection and HVDC transmission, the use of a medium- or high-frequency transformer can reduce converter size and weight. The configuration described in the reviewed work had not yet been implemented at the time of publication, so it represents a proposed architecture rather than an established practical alternative.

4. Series DC connection with HVDC transmission

In a series-connected design, turbine-side DC outputs are connected in series to build the transmission voltage. This can eliminate the centralized offshore substation used to house major step-up and conversion equipment, making the concept attractive where offshore platform size and cost are priorities.

Series connection brings a critical insulation challenge: the turbine farthest from ground may need to withstand the full transmission voltage. Options include insulating the generator and converter for that potential, placing the turbine tower at high potential, or using transformers to provide isolation. Conventional low-frequency transformers can be bulky and heavy in the limited space available in a turbine.

Proposed VSC- and pulse-width-modulated current source converter (PWM CSC)-based approaches offer fast response and independent active and reactive power control. A medium-frequency transformer (MFT)-based design uses a modular DC/DC converter to address both generator-side control and insulation. Its modular cells share the megawatt-level conversion task, allowing each transformer to handle only part of the power. The MFT approach is intended to reduce transformer size and weight compared with low-frequency alternatives.

What the architecture choice means for project teams

Configuration selection is a system-level decision, not simply a choice between AC and DC cables. Teams must weigh transmission distance and power capacity alongside converter requirements, reactive power needs, insulation, reliability, and offshore space and weight constraints.

  • For shorter links: parallel AC collection with HVAC can offer a straightforward, economical arrangement, while accounting for reactive power compensation.
  • For distant, high-capacity projects: parallel AC collection with VSC-HVDC provides controllability but requires substantial offshore conversion infrastructure.
  • For reduced offshore platform dependence: series DC concepts are attractive, but generator insulation and turbine-level equipment require careful engineering.
  • For transformer size and weight: MFT-based designs offer a potential alternative to bulky low-frequency transformers, though the configuration described is a proposed design.

Conclusion

Offshore wind farm configurations involve balancing transmission performance against the cost, footprint and complexity of electrical equipment. HVAC can suit shorter connections, while HVDC supports long-distance transmission but may require significant conversion infrastructure. Series-connected designs could reduce reliance on a large offshore substation, but they introduce demanding insulation requirements. For project teams, comparing these trade-offs early helps align the electrical architecture with transmission needs and the practical limits of offshore installations.