A programmable growth chamber can do more than maintain temperature and humidity. For industrial automation engineers, system integrators and biological production teams, it can provide a test environment for measuring how organisms respond to climate, lighting and resource availability. A modular chamber design combines environmental sensing, climate control, gas and liquid exchange, adjustable lighting and experiment automation in one system.
This approach addresses a limitation of conventional commercial chambers: although some provide climate regulation and sensor access, infrastructure for controlled resource exchange and flexible experiment automation may be limited. A configurable testbench can support quantitative studies of plants, fungi and insect larvae, helping teams collect data on growth conditions and exchanges of gases, water and nutrients.
Why use a programmable growth chamber?
Controlled-environment agriculture—including vertical farming and plant factories with artificial lighting—depends on creating a suitable microclimate. These systems can use land and water differently from conventional farming, but maintaining an artificial environment also requires energy. Improving production therefore calls for a better understanding of how organisms use resources and how environmental conditions affect biomass and byproducts.
That understanding begins with repeatable experiments. Researchers need to control factors such as temperature, humidity, light spectrum and gas concentration while recording conditions inside the growing environment. They may also need to supply water or nutrients and exchange gases without opening the chamber and disrupting the test conditions.
Commercial equipment can be costly or difficult to adapt to specialized experiments. A modular design built from off-the-shelf components and custom parts offers another route: assemble the functions required for a particular study, then configure the control application for the organism and experimental regime.
Core hardware: sensing, conditioning and exchange
Air conditioning and humidity
The chamber design uses a thermoelectric cooler (TEC) for heating or cooling. Changing the polarity of the voltage changes the TEC’s operating mode; a driver circuit provides this control, while a filter smooths the pulse-width-modulated signal. Fans circulate chamber air, and a water-cooled heat exchanger removes heat from the opposite side of the TEC.
Cooling can also condense water, which is collected in a reservoir. An ultrasonic atomizer then uses that water to increase humidity. This combines temperature conditioning and humidification in a compact module, although testing also identified thermal insulation as an area for improvement. In the reported setup, heating raised chamber temperature more effectively than cooling lowered it relative to ambient conditions.
Gas, water and nutrient exchange
Measurements of oxygen, carbon dioxide and water vapour can help characterize biological activity. But accurate measurements require a sealed chamber, while organisms still need access to air, water or nutrients. Membrane pumps address this by moving gases and liquids through dedicated lines while the chamber remains closed.
Separate pump paths support gas removal and replenishment, water supply to a reservoir or growing medium, delivery of a water-and-nutrient mixture, and drainage to an external reservoir. The arrangement makes resource exchange an actuator function rather than a manual interruption to the experiment.
Adjustable lighting and sensor coverage
Different organisms can have different lighting needs, and the effect of spectral composition may itself be a subject of study. The prototype lighting system combines white LEDs with independently controlled red, blue and green channels, with provision for additional wavelength channels. PWM control adjusts the channels, while relays switch groups of LED modules.
The sensor cluster measures variables including CO2, O2, volatile organic compounds, air temperature, substrate temperature, relative humidity, pressure and growing-medium moisture. Separating substrate sensors from the main sensor unit allows them to be placed where measurements are needed. Sensor selection and placement should reflect the experiment: the system’s tests, for example, identified a need for a more robust moisture sensor.
Automation architecture supports repeatable experiments
The software is organized into three layers: embedded firmware on the controller, a cloud platform for data aggregation and user interaction, and an application-development framework for defining experiment regimes. The microcontroller manages sensors and actuators, schedules measurements, logs data locally and communicates with external systems.
For users who do not want to write embedded C or C++ applications, a model-driven development workflow based on MATLAB Simulink can generate application code and a corresponding web interface. The cloud platform can display measurements, support diagnostics and provide access to application-specific settings. This separation lets experiment logic change without requiring users to manage every hardware detail.
Example control functions include PID temperature control, hysteresis-based humidity or CO2 control, cyclic ventilation and a time-based lighting routine. The prototype’s lighting control operates open-loop because it does not measure radiant flux. As a result, the system can vary channel outputs according to a programmed schedule but cannot use sensor feedback to correct changes in actual light output.
What validation demonstrated
Automated tests assessed the TEC, humidifier, gas exchange and lighting functions, followed by experiments with basil plants and black soldier fly larvae. In the plant study, chamber measurements tracked temperature, humidity and CO2 under programmed lighting and ventilation. In the larval study, air and substrate temperatures and gas concentrations were monitored as the larvae developed.
These trials demonstrated how the chamber can collect time-series data while running configured control routines. They also exposed practical limits: humidity readings may require correction for sensor self-heating, gas exchange affects chamber humidity, and thermal performance depends partly on insulation. The trials are demonstrations of measurement and control capability, not universal conclusions about organism growth.
Practical implications for automation teams
A modular growth chamber offers a flexible platform for testing how biological processes respond to controlled conditions. For engineering teams, its value lies in integrating sensing, actuation, data logging and experiment logic—not simply in maintaining a setpoint. Before adapting this approach, teams should define the variables they need to measure, the resources they must exchange, the required control sequences and the limitations of their sensors.
With those requirements established, a programmable growth chamber can support repeatable studies across different organisms and experimental regimes. The resulting measurements can inform process models, control strategies and decisions about resource use, while modular hardware and open software make the setup easier to adapt as research or production questions change.