Nonlinear loads can distort supply current and reduce power quality in industrial and commercial electrical systems. A shunt active power filter offers one approach to addressing this problem: an auxiliary converter operates alongside the nonlinear load and is controlled to compensate for harmonic current. A MATLAB/Simulink study compared proportional-integral (PI) and fuzzy logic control of this arrangement for a single-phase diode bridge rectifier.
The comparison is useful for engineers evaluating converter-based harmonic mitigation. It illustrates how the controller used to switch an auxiliary converter can affect simulated total harmonic distortion (THD), while also highlighting the need to interpret reported results in the context of the model and its assumptions.
Why nonlinear loads create power quality problems
A linear load supplied by a sinusoidal source draws a sinusoidal current. With a nonlinear load, the relationship between voltage and current is different: the load can draw a distorted current even when the supply voltage remains sinusoidal. Rectifiers and variable frequency drives are examples of equipment associated with nonlinear-load behavior. The study focuses on a single-phase diode bridge rectifier operating as an unregulated converter.
Distorted current contains harmonics—frequency components beyond the fundamental supply frequency. As nonlinear loads become more prevalent on a network, their combined harmonic currents can contribute to waveform distortion. The paper also identifies possible effects such as incorrect utility-meter readings and damage to components including circuit breakers and fuses.
Passive filters can compensate for harmonics, but their tuning to particular frequencies limits their operating range. The study instead investigates an active filtering arrangement whose switching is controlled to respond to the required compensation.
How the shunt active power filter works
The proposed configuration places a synchronous link converter (SLC) in shunt with the primary converter, which is the diode bridge rectifier and its resistive load. The SLC uses a switching device, identified in the paper as an IGBT. A controller determines its gate-pulse timing and therefore the device’s turn-on and turn-off times.
The aim is to divide the current between the primary and auxiliary converters so that the main converter receives most of the active power, while the SLC handles the harmonic and reactive-current components associated with the nonlinear load. In the intended operation, the combined input currents are sinusoidal and in phase with the source voltage. Bringing source current and voltage into phase also supports improved power factor.
In practical terms, this is a parallel power-processing strategy: the auxiliary converter is not simply a replacement for the rectifier. It is controlled to compensate for aspects of the rectifier’s input current that degrade the supply-side waveform.
Comparing PI and fuzzy logic control
PI controller
In the PI-controlled case, the controller governs the SLC switching to reduce the harmonic content drawn by the nonlinear load. The simulations report a substantial reduction in source-current distortion compared with the uncompensated rectifier. However, the paper gives different PI THD figures in different sections: the results discussion cites 17.9%, while the comparison table lists 12%. Both are presented as simulated outcomes, so the discrepancy should be resolved against the original model or data before using either value as a design benchmark.
Fuzzy logic controller
The fuzzy logic controller is used to control the SLC’s IGBT gate pulse as well. In the reported simulation, the source current becomes more nearly sinusoidal, and THD falls to 5%. This is lower than either PI figure reported in the paper. The comparison therefore suggests that fuzzy logic control performed better in this particular modeled case; it does not establish that it will outperform PI control in every installation or operating condition.
The study’s comparison covers four cases: a linear load, the nonlinear rectifier without compensation, the rectifier with SLC and PI control, and the rectifier with SLC and fuzzy logic control. It reports a supply voltage of 311.13 V and line current of about 3.2 A across the cases. The uncompensated nonlinear-load case has THD of approximately 117% (also described as 117.8% in the text), compared with 5% for the fuzzy-controlled case.
What the simulation results mean for engineers
The results demonstrate the potential of controlled shunt compensation to improve the source-current waveform in a modeled single-phase rectifier system. They also show why controller selection matters: different control strategies can produce different simulated levels of harmonic reduction in the same general converter arrangement.
For system integrators and technical decision-makers, the findings are a starting point for evaluation, not a substitute for application-specific engineering. The study uses MATLAB/Simulink simulation; it does not establish field performance across different loads, system configurations, or operating conditions. Before selecting a control strategy, engineers should validate the model against the intended electrical system and confirm the relevant performance measures. The conflicting PI THD figures are a further reason to check the underlying simulation results rather than treating a single number as definitive.
Conclusion
A synchronous link converter operating as a shunt active power filter can be controlled to compensate for harmonic current from a nonlinear rectifier load. In the reported simulations, both PI and fuzzy logic control reduced distortion, while the fuzzy-controlled case reached a reported THD of 5%. The practical takeaway is to assess the complete converter-and-controller arrangement in the context of the target load, verify simulation results carefully, and treat reported THD values as model-specific evidence rather than guaranteed outcomes.