A Type 3 wind turbine model represents a doubly-fed induction generator (DFIG) and its interaction with the power network. For engineers evaluating grid behavior, the model must capture more than energy conversion: wind-speed response, converter controls, synchronization and protection all influence the simulated result. In PSCAD, a DFIG model can use detailed or average converter representations, depending on the study’s focus and the level of switching detail required.

How a Type 3 wind turbine model represents the system

The model combines mechanical and electrical subsystems, with the induction machine linking them. On the mechanical side, the turbine extracts energy from the wind and produces shaft torque. On the electrical side, the machine and back-to-back AC-DC-AC converters transfer power to the grid and regulate operating conditions.

The mechanical model estimates available wind power using air density, rotor swept area, wind speed and a power coefficient. That coefficient depends on tip-speed ratio and blade pitch angle. A maximum-power-point strategy adjusts the turbine operating point to capture available energy, while respecting equipment limits. When wind speed rises above the rated range, the pitch controller increases blade angle to reduce aerodynamic power. The example model sets power to zero outside its configured cut-in and cut-out wind-speed limits.

The electrical system includes the rotor-side converter (RSC), grid-side converter (GSC), DC link, controllers, AC filter and protective devices. The GSC regulates DC-link voltage and can control reactive power. The RSC controls rotor currents to manage active power and either reactive power or terminal AC voltage, according to its selected control mode.

Choosing between detailed and average converter models

Converter representation is a central modeling decision. A detailed model represents the two-level converters with IGBT switches and pulse-width modulation. It can capture switching-related harmonics and transient behavior, but resolving the switching events requires a small simulation time step and increases computational effort.

An average converter model replaces the switching circuit with equivalent controlled voltage and current sources. It preserves the converter’s broader power-transfer behavior without explicitly representing individual switching events. This allows a larger time step and can reduce simulation time, but switching harmonics and some fast converter transients are not fully represented. It is therefore more appropriate when the study focuses on slower system dynamics rather than switching effects.

The PSCAD example compares the two representations under changes in wind speed and a three-phase-to-ground fault. Its reported responses are similar for those cases, while the average model runs faster in the wind-speed study. That comparison applies to the modeled system and test conditions; engineers should select the model based on the phenomena and fidelity required for their own study.

Control and start-up sequence

Starting the electrical system in a controlled sequence helps establish the DC bus and synchronize the generator before power transfer. In the example, the induction machine initially operates in speed-control mode near its intended steady-state speed. After the grid connection breaker closes, the GSC is deblocked first and regulates the DC voltage. The RSC is then deblocked to establish a machine stator voltage suitable for connection.

A synchronizer checks the voltage magnitude across the stator-side breaker. Once the voltage condition is met, the breaker closes and the RSC transitions to active- and reactive-power or AC-voltage control. This is one implementation approach, not the only possible start-up method. Its sequence and thresholds should be reviewed against the requirements of the modeled system.

During normal operation, converter current controllers work in d-q reference frames. These separate current components so that active- and reactive-power objectives can be managed through their respective control loops. Current limits constrain converter output, an important consideration when voltage falls during a disturbance. The example GSC can prioritize either d-axis or q-axis current, so the selected priority affects how its limited current capacity is allocated.

Protection during grid disturbances

Crowbar protection

A DFIG’s stator is directly connected to the grid, so faults can induce high currents in the rotor circuit. The crowbar protects the rotor-side converter by short-circuiting the rotor terminals through a resistance. In the example, activation can be triggered by excessive rotor current or DC-link voltage, and the crowbar operates for a defined period.

While the crowbar is active, the converter cannot provide the same reactive-current support as it can after the protection is removed. This creates a practical coordination issue: protection must limit converter stress while allowing the turbine to resume grid-support functions when conditions permit. The appropriate activation logic and duration depend on the study assumptions and applicable grid requirements.

DC-link chopper and AC filter

A DC-link chopper uses a controlled resistor to dissipate energy when DC voltage exceeds its activation threshold. Hysteresis control switches the chopper on and off around defined voltage levels. Separately, an AC filter on the grid-side converter reduces the impact of converter-generated harmonics. Its components must be selected with attention to resonance and damping, rather than treating the filter as an isolated add-on.

Practical implications for simulation studies

For power-system studies, model selection should follow the question being asked. Use a detailed converter when switching behavior and harmonics matter; consider an average representation when the emphasis is on slower dynamics and broader fault response. In either case, check that machine ratings, converter limits, wind and pitch settings, control modes, start-up logic and protection thresholds match the intended scenario.

A Type 3 wind turbine model is most useful when its mechanical, electrical and protection elements are considered together. Understanding how these parts interact helps engineers interpret simulation results, choose an appropriate level of detail and assess grid response without mistaking a model’s assumptions for universal turbine behavior.