Access Official Technical PDF

Share Summary:LinkedInEmail

Remote electrification requires more than choosing a renewable generator. System planners must account for local energy resources, changing demand, storage needs and the practical constraints of operating far from an established grid. A case study for Keteira, a village on Moala Island in Fiji, used HOMER Pro to compare renewable power system options and model a hybrid mini-grid for an estimated 35 homes.

The analysis identified a combination of biomass, wind, solar photovoltaics (PV) and battery storage as the lowest-cost option among the systems evaluated. Its results offer a useful example of how resource diversity can be incorporated into off-grid planning, while also showing why modeled outcomes need to be checked against site conditions before investment decisions are made.

Why remote electrification calls for a local solution

Extending a central grid to isolated islands can be difficult where communities are geographically dispersed and transport links are limited. The case study notes that many Fijian islands outside the main grid areas rely on off-grid systems, including diesel or biofuel generators, solar home systems and mini-grids. Fuel delivery and replacement parts can be time-consuming and expensive in remote locations.

For communities, electricity supports services and activities such as lighting, communications, education, health care and water supply. A village-scale system therefore needs to do more than produce energy in theory: it must be designed around an estimate of when and how people will use electricity, and provide a supply suited to those needs.

Estimating demand and available resources

Because a field visit to Keteira could not take place, the study estimated daily electricity demand using consumption patterns from communities with similar living standards. It also developed an hourly demand profile for the village. This provided a modeled basis for sizing and comparing generation options, but it was not a measurement of actual household consumption in Keteira.

The analysis considered three renewable resources identified for Moala Island: solar, wind and biomass. Resource potentials were estimated using online global data libraries. Such inputs allow an initial system comparison when local measurements are unavailable, but they remain assumptions that should be verified as part of project development.

Six system alternatives were developed, including options based on individual energy sources and hybrid configurations. The alternatives were evaluated and optimized in HOMER Pro using the levelized cost of electricity (LCOE) as a comparison measure. LCOE provides a way to assess modeled electricity costs over a system’s lifetime, while the capital expenditure (CAPEX) estimate indicates the initial investment required for installation.

Remote electrification: why the modeled system was hybrid

The option with the lowest modeled LCOE combined biomass, wind, solar PV and battery storage. The system was designed to meet the estimated maximum power demand and daily energy demand. In the model, the different components contribute to the overall supply rather than relying on a single renewable resource.

This configuration reflects a central planning consideration for off-grid power: renewable generation can vary with resource availability. Solar output depends on sunlight, while wind generation depends on wind conditions. Battery storage can shift some generated electricity to a different time, but it is not itself a source of energy. Including several generation types gives the model more than one resource to draw on when meeting the estimated load.

The study calculated an LCOE of 0.516 USD/kWh for the selected hybrid system and estimated installation CAPEX at 480,500 USD. These figures belong to the study’s modeled assumptions and should not be treated as a confirmed project price or a guaranteed electricity tariff.

What the findings mean for project planning

For engineers, system integrators and energy planners, the case illustrates a practical sequence for evaluating a remote mini-grid:

  • Build a demand profile. Estimate not only daily energy use, but also the timing and peak level of demand.
  • Assess local resources. Compare the availability of solar, wind and biomass using the best data available, and identify where local verification is needed.
  • Compare system configurations. Evaluate single-source and hybrid options against consistent demand and cost assumptions.
  • Include storage in the system model. Consider how battery charge and discharge interact with generation and demand.
  • Separate modeled results from validated results. Treat cost and system sizing as provisional until key inputs are confirmed.

These steps matter to operational decision-makers as well as designers. The selected mix affects what equipment must be installed, how the system is operated, and what resources and maintenance arrangements will be needed. The case study does not establish detailed operating procedures or component specifications, so those would require further project-level design.

Why field validation remains essential

The authors explicitly cautioned that the proposed system might not be optimal for Keteira’s real conditions because no field study could be conducted. The demand profile was estimated from other communities, and renewable resource potentials came from global data sources. Local measurement and direct assessment could therefore change the assumptions used in the model and, in turn, the preferred system configuration or cost estimate.

Before moving from feasibility analysis to implementation, planners would need to test the model’s assumptions against conditions in the village. That includes confirming demand, assessing the actual availability of the identified resources, and reviewing the costs and practical requirements relevant to installation and operation. The study presents an analytical starting point, not a final engineering design.

Conclusion

The Keteira case shows how HOMER Pro can be used to compare renewable options for remote electrification and identify a candidate hybrid system. In this analysis, biomass, wind, solar PV and battery storage produced the lowest modeled LCOE among six alternatives. The estimated cost provides a basis for discussion, but its reliability depends on assumptions that were not verified through fieldwork. For project teams, the key takeaway is to use modeling to guide system selection—and validate local demand, resources and costs before committing to a design.

Access Official Technical PDF