Choosing small hydropower generators is an engineering decision that affects how a plant manages voltage, frequency, reactive power and changing operating conditions. The options include synchronous, induction, double-fed and inductor generators, each with different strengths and limitations. The right choice depends on the turbine’s power and rotational speed, the site’s water head and flow, the electrical load, and the technical and economic requirements of the installation.

Small hydropower can supply electricity to communities and other consumers near rivers and water conduits. In Armenia, for example, an analysis of 40 operating plants rated from 1 to 5 MW reported water heads ranging from 51.2 to 575 metres and flows from 0.45 to 6 cubic metres per second. That variation illustrates why generator selection needs to be matched to the specific hydro unit rather than treated as a one-size-fits-all decision.

Small hydropower generators: key selection factors

Generator characteristics shape how a plant behaves in both grid-connected and standalone operation. Synchronous machines offer strong voltage-control capabilities, while induction machines can provide a simpler, lower-cost option in suitable applications. Double-fed machines use a frequency converter to enable speed and power regulation, and inductor generators offer a different rotor design that can help match generator and turbine speeds.

Before selecting a machine, designers and plant operators should consider:

  • Turbine power and speed: The generator must suit the hydro turbine’s operating range. Low-speed applications may require a suitable multipole generator or a speed-matching arrangement.
  • Electrical operating mode: Requirements differ between operation in parallel with a power network and operation on an autonomous load.
  • Control needs: Voltage, frequency and active or reactive power may need to be regulated differently depending on the generator type and system configuration.
  • Installation economics: Initial cost, size, weight, maintenance needs and the additional equipment required all affect the overall choice.

Comparing generator types

Synchronous generators

Synchronous generators are used across a broad range of small hydropower plant ratings. Their advantages include high efficiency, a close relationship between shaft speed and output frequency, and the ability to generate reactive power. They also allow straightforward and accurate voltage regulation when operating with a standalone load.

These control benefits come with greater structural complexity than some alternatives. A conventional synchronous machine has a rotor excitation winding and an excitation supply system, which can increase its size, weight and cost. Brushless excitation is used in many applications, but it does not remove all of the machine’s structural complexity.

At lower plant ratings, a suitable low-speed generator may not be available. General-purpose synchronous generators can then be used with a speed increaser to match the generator’s rotational speed to the turbine. This adds a mechanical component that should be considered during system design.

Synchronous machines also use damping windings to reduce rotor oscillations caused by abrupt operating changes, including changes in turbine torque. An external damper system has also been proposed for a synchronous hydro unit: an asynchronous machine with a phase rotor is installed on the unit shaft and operates alongside the internal damper. Its intended role is to reduce oscillation amplitude and support stability.

Permanent-magnet synchronous generators

Permanent-magnet generators have a simpler rotor arrangement because they do not require a rotor excitation winding. However, their output voltage is difficult to regulate, so they are commonly used with rectified loads where that limitation is acceptable. Permanent magnets add cost, and their installation can make rotor construction more complex. The available power range and suitability for low-speed, low-power applications should be checked for the particular design.

Induction generators

Induction generators can be used across many small-hydropower power ranges. Their relatively simple construction can make them less costly, lighter and smaller than synchronous generators of comparable power. They are also described as having low sensitivity to short circuits and a high degree of protection from external impacts.

The main trade-off is reactive power. When connected in parallel with a network, an induction generator consumes reactive power. For standalone operation or connection to a weak network, capacitor banks are used to provide it. These capacitors add cost and affect the system’s size and weight. Voltage and frequency regulation can also be difficult in autonomous operation. The required capacitor capacity depends on the load: an active load may require a relatively modest bank, while an inductive load must also be supplied with reactive power.

Double-fed machines

A double-fed machine is an induction generator with a wound rotor. Its stator connects to the network, while a frequency converter supplies the rotor. By adjusting the rotor supply frequency, the system can regulate shaft speed and support synchronous operation with the power system across a range of speeds.

The converter enables control of active power and can support adjustment of reactive power. Because the converter processes only part of the generator’s electrical power, it need not be rated for the machine’s full output. This arrangement can provide fast regulation and favorable dynamic behavior, although the generator and converter must be considered together as a system.

Inductor generators

An inductor generator is a type of synchronous generator with a rotor that has no winding and an excitation winding located on the stator. The design avoids a rotor excitation contact system and can offer a mechanically simpler rotor. It retains synchronous-machine characteristics, including the relationship between frequency and rotational speed and the potential for reactive-power generation when operating in parallel with a network.

Its toothed rotor can provide magnetic speed reduction, helping match generator speed to turbine speed without a mechanical speed increaser. The key drawback identified for this type is low efficiency, which can limit its suitability to small-power hydro systems.

Make the choice around the whole hydro unit

No generator type is best in every small hydropower application. Synchronous generators provide useful control and efficiency characteristics; induction generators may suit projects prioritizing simpler construction and lower capital expense; double-fed systems offer a way to regulate operation through a converter; and inductor generators may help with speed matching but require careful consideration of efficiency.

The practical selection should account for turbine power and rotational speed, water head and flow, operating mode, load characteristics, and the installation’s technical and economic constraints. Evaluating the complete hydro unit—not just the generator’s nameplate—helps ensure that control requirements, auxiliary equipment and operating trade-offs are addressed before equipment is chosen.