Access Official Technical PDF

Share Summary:LinkedInEmail

Wideband transmission line modeling is important when engineers assess variable-frequency drives (VFDs) and other power-electronics systems with fast switching. An inverter’s pulse-width-modulated output contains steep voltage edges, and the cable between the inverter and motor may behave as more than a simple electrical connection. It can introduce reflections, waveform distortion and conducted electromagnetic interference (EMI). The delay-rational Green’s-function-based (DeRaG) model was developed to represent these behaviors across a wide frequency range while remaining usable in time-domain simulation.

Why VFD cables need transmission line models

A VFD typically combines an inverter, a motor and a connecting power cable. The inverter uses switching devices such as insulated-gate bipolar transistors (IGBTs) and pulse-width modulation (PWM) to control the motor’s voltage and frequency. Although the motor responds mainly to the fundamental component of the output waveform, the switching waveform also includes fast transitions with high-frequency content.

When a cable is electrically long relative to the wavelengths associated with a signal, propagation effects matter. The cable can store and transfer energy along its length, and a signal takes time to travel from one end to the other. Impedance mismatch between the cable and motor can cause reflections, potentially producing voltage peaks at the motor terminals. Coupling between conductors can also contribute to current spikes, while parasitic capacitances provide paths for high-frequency common-mode currents.

These effects make cable behavior relevant to drive performance, motor insulation and bearings, overcurrent alarms, and interference affecting other equipment. An electromagnetic assessment therefore needs a cable representation that captures propagation and coupling, rather than treating the cable only as a lumped component.

What a multiconductor transmission line model represents

Multiconductor transmission line (MTL) theory describes several parallel conductors relative to a reference conductor. Under the quasi-transverse-electromagnetic assumption, voltage and current vary with both position along the line and time. The line’s electrical behavior is represented by per-unit-length resistance, inductance, capacitance and conductance matrices. These parameters may be frequency independent or frequency dependent.

The telegrapher’s equations describe how voltage and current change along the line. In the frequency or Laplace domain, these equations can be handled as ordinary differential equations. But system-level studies often need time-domain results, particularly when the model is connected to nonlinear devices such as inverter power transistors.

Different MTL modeling approaches make different trade-offs. Lumped segmentation is straightforward to apply, but electrically long lines may require many sections and the approach does not inherently represent propagation delay. Other techniques—including the method of characteristics, finite-difference time-domain methods and rational approximation—address line behavior in different ways. The DeRaG approach focuses on representing delay explicitly alongside a compact approximation of the remaining line response.

How the DeRaG model supports wideband analysis

In the DeRaG model, the line’s impedance or admittance is expressed as a rational series together with a hyperbolic part. The rational series is formed from poles and residues and represents frequency-dependent behavior that can be implemented in a state-space form. Delay extraction identifies and incorporates propagation delays so that the rational series can be truncated without discarding the line’s essential high-frequency behavior.

The hyperbolic component retains key information about propagation and attenuation. This combination is the basis for the model’s wideband character: the line is not represented solely by a finite rational fit that approximates delay over a limited frequency range. The delay is explicitly included, while the rational terms describe additional dynamics.

The model is formulated independently of the line’s sources and terminations. This allows the same line representation to be connected to different circuit conditions in a simulation. The approach also accommodates frequency-dependent per-unit-length parameters, extending its use beyond cases where cable properties are treated as constant with frequency.

Including electromagnetic interference

In a VFD installation, conducted noise can travel through cables, grounding paths and other conductive structures. The DeRaG framework can be extended to account for electromagnetic interference caused by plane-wave coupling to an MTL. This is relevant when assessing how an external electromagnetic field can induce responses on a cable system.

Representing this coupling alongside the line’s transmission behavior helps engineers consider both the cable’s role in carrying disturbances and its susceptibility to external interference. It does not remove the need to model the rest of the drive: a complete assessment also depends on suitable representations of the inverter and motor.

Bringing the model into simulation workflows

Many advanced transmission-line models have been adapted for SPICE-like transient solvers. However, power-electronics engineers and system integrators also use system-level environments such as Simulink. The DeRaG model was implemented in both SPICE and Simulink, broadening the range of workflows in which it can be applied.

This matters because a cable model must be usable within the larger system being assessed. In a drive simulation, the transmission line can be connected to switching circuitry and motor-side conditions, enabling time-domain analysis of interactions that are difficult to represent with a cable-only lumped approximation. The Simulink implementation was described as simple to construct, offering a route for incorporating the model into system-level studies.

Using the model to interpret line behavior

Beyond simulation implementation, the hyperbolic part of the formulation can help characterize MTL behavior. The work used this component to derive a distortionless condition for multiconductor lines, extending the concept beyond the familiar single-conductor Heaviside condition. This provides a theoretical way to assess whether a line’s propagation preserves signal shape, rather than considering only the response of one conductor pair.

For practical engineering teams, the value is twofold: a model can support time-domain system analysis, and its mathematical structure can offer insight into why a line produces attenuation, delay or distortion.

Practical implications for automation teams

VFD cable behavior should be part of electromagnetic and transient analysis when switching edges and cable lengths make propagation effects significant. The DeRaG approach brings together explicit delay, rational modeling and a hyperbolic representation of high-frequency behavior, with extensions for frequency-dependent line parameters and plane-wave interference.

For engineers and technical decision-makers, the practical implication is to select a cable model that matches the analysis objective and simulation environment. A suitable wideband MTL representation can help reveal reflections, distortion and conducted interference within a broader drive model, supporting more informed evaluation of power-electronics systems and their cable connections.

Access Official Technical PDF

About The Author