An isolated power and data interface can help a loop-powered transmitter protect measurement integrity without consuming an excessive share of its limited current budget. In a 4–20 mA installation, the sensor may be connected to grounded equipment while the receiver references a different ground. Over long cable runs, those conditions can create unwanted ground loops that affect the measurement signal.
A reference design from Texas Instruments, TIDA-010018, demonstrates one approach for low- and ultra-low-power transmitter electronics. It combines isolated power conversion and digital signal isolation with non-isolated power rails, using low-quiescent-current switching regulators and LDOs. The design is intended for evaluation and adaptation; its documented operating limits and isolation properties must be considered when applying it to a specific system.
Why isolate a loop-powered transmitter?
In a two-wire 4–20 mA transmitter, power and measurement data share the loop. The transmitter may be hundreds or thousands of meters from the receiver, and its sensing element—for example, a thermocouple—may be connected directly to a grounded metallic object. Meanwhile, the receiver and loop input are referenced to the receiver’s ground.
Separating the sensor front end electrically from the loop-side electronics helps break the ground-loop path. An isolated DC/DC converter supplies the sensor-side circuitry from an isolated rail, while a digital isolator carries signals across the isolation boundary. The result is a distinct isolated side and non-isolated side, each with its own ground reference.
That separation must fit within the transmitter’s power budget. The design documentation cites a 3.8–20.5 mA measurement range under the NAMUR NE 043 recommendation and notes that transmitter electronics are generally designed to draw less than 3.6 mA. The practical challenge is therefore to power the sensor front end, processing and output circuitry while reserving sufficient current for the loop signal.
Isolated power and data interface architecture
TIDA-010018 takes a 5 V input and generates both isolated and non-isolated rails. In a typical loop-powered system, a pre-regulator derives that 5 V supply from the 8–36 V loop. The reference design itself requires a current-limited input: its specified maximum source rating is 5.25 VDC and 30 mA. The design documentation also cautions that the board is for parameter evaluation, not isolation-voltage testing.
On the non-isolated side, a buck converter provides a 3.3 V rail, with a 3.0 V LDO option for post-regulation. On the isolated side, an isolated DC/DC stage supplies the isolated power path, followed by an isolated buck converter for a 3.3 V rail and an optional 3.0 V LDO. Each output path is rated for a maximum total output current of 10 mA; this is a design limit, not a per-device allowance.
The isolated DC/DC converter reaches a stated peak efficiency of 86.5% at an output current of 4–5 mA. The non-isolated buck is specified at up to 93% efficiency, and the isolated buck at up to 92%. Actual efficiency varies with operating conditions and load, so engineers should use the detailed design specifications when sizing the complete power budget.
Choosing between buck efficiency and LDO noise reduction
The reference design allows the user to select either a buck output or an LDO-regulated output on each side. Using the buck directly reduces the additional losses associated with linear post-regulation and is the higher-efficiency option described by the design. The tradeoff is greater output ripple than when an LDO is used.
An LDO can reduce the remaining ripple from the upstream buck, making it useful where the analog front end or other sensitive circuitry needs a quieter supply. The design specifies 3.0 V LDO outputs and reports 16 µA quiescent current at a 1 mA output load, with power-supply rejection above 36 dB at frequencies up to 200 kHz. Choosing an LDO therefore involves balancing noise performance against the extra power consumed in the regulation stage.
Startup behavior also matters in a tightly current-limited design. The LDO’s output ramp requires current, supplied by the LDO and its upstream buck; connected load and bypass capacitance add to that demand. If input voltage falls far enough to reach an upstream converter’s undervoltage lockout threshold, the rail may need repeated startup attempts. System-level testing should include startup, load changes and the actual source current limit.
Four isolated data channels for common interfaces
The digital isolation block provides three channels from the non-isolated side to the isolated side and one channel in the reverse direction. This arrangement can support signal paths used by interfaces such as SPI, I2C and UART, subject to the needs of the application and the selected device configuration.
The design uses the ISO7041 digital isolator, which is specified for low-power CMOS or LVCMOS signals. Its documented per-channel current figures are 5, 16 and 130 µA at data rates of 10, 100 and 1,000 kbps, respectively, in the reference design feature summary. Since dynamic consumption depends on data rate, engineers should account for communication activity—not only idle current—when estimating total transmitter demand.
Practical design checks
- Budget current across both sides. Include the sensor front end, processor, data isolator, regulator losses and loop interface.
- Select rail quality deliberately. Use a buck rail where efficiency is the priority, or evaluate the LDO option where lower ripple is needed.
- Check startup margin. Consider input current limits, regulator enable thresholds, output capacitance and downstream load during power-up.
- Verify isolation for the application. Functional isolation depends on the transformer, digital isolator and board construction. The reference design is not intended for isolation-voltage testing.
Conclusion
For loop-powered instrumentation, isolation is both a grounding strategy and a power-management problem. TIDA-010018 illustrates how an isolated DC/DC supply, low-quiescent-current buck converters, optional LDO post-regulators and a four-channel digital isolator can be combined for low-power transmitter applications. The practical design decision is to match rail voltage, ripple, data activity and startup behavior to the available current while verifying that the isolation implementation and operating limits suit the end system.