Ex eb indicators provide an alternative approach to displaying process values in hazardous areas. For instrumentation engineers and system integrators, the key is understanding how the protection methods work together—and what that means for loop design, wiring, equipment selection and maintenance. The BA304SG and BA324SG loop-powered 4–20 mA indicators illustrate this approach for Zone 1 and Zone 2 gas applications, with additional certification for specified dust environments.

How Ex eb indicators protect display instrumentation

Increased safety protection, designated Ex eb, is intended to reduce the likelihood of excessive temperatures, arcs and sparks. Equipment with Ex eb protection and equipment protection level Gb can be installed in Zones 1 and 2. Unlike the Ex ec level used for Zone 2, Ex eb does not permit unprotected electronic components inside the enclosure.

To address that limitation, the described indicator design combines three protection techniques. The Ex eb enclosure provides environmental protection and contains approved terminals for field wiring. An Ex mb encapsulated assembly protects energy-limiting components and provides an intrinsically safe output. The display electronics and push-button controls are supplied from that output and use Ex ib intrinsic safety protection.

This combination is important in practical terms: the instrument is designed for Zone 1 without relying on a Zener barrier or galvanic isolator, and it has no entity or cable parameters. However, it must not be treated as an intrinsically safe loop. The guide permits connection in series with hazardous-area 4–20 mA loops using explosion-protection methods other than intrinsic safety.

Where the approach fits

The BA304SG has a four-digit display; the BA324SG has a five-digit display and a 31-segment bargraph. Both are available in GRP or stainless-steel enclosures. The guide presents these instruments as alternatives to certified Ex d flameproof indicators in Zones 1 and 2, and as alternatives to Ex nA instruments in Zone 2.

Compared with many flameproof indicators, the stated design advantages include a larger display, tactile controls that can be operated in the hazardous area, lower weight and the use of Ex e cable glands. The enclosure-based approach also supports dust protection, subject to the applicable certification and installation requirements. These are selection considerations, not a reason to assume that every Ex d or Ex nA installation can be changed without a review of the hazardous-area documentation.

Ex eb indicators and 4–20 mA loop design

Loop voltage budget is central to specifying a series-connected indicator. The guide gives a maximum input voltage of 30 V DC. At 20 mA, the indicator introduces a voltage drop of less than 2.9 V; with the loop-powered backlight, the maximum stated drop is less than 5.6 V.

Before installation, confirm that the supply can meet the minimum voltage requirements of every device in the loop while accounting for cable and receiving-equipment drops. For example, the guide’s simplified loop assigns 8.0 V to a two-wire transmitter, 2.9 V to the indicator, 0.2 V to cable resistance and 5.0 V to the safe-area load. These drops total 16.1 V, so the supply must provide at least that voltage and must not exceed the indicator’s 30 V maximum. Using the backlight raises the example’s minimum supply requirement to 18.8 V.

The certification also calls for a suitable SELV or PELV supply, or an adequately approved supply providing the required double or reinforced insulation. Check the instrument certificate and applicable installation documentation for the requirements governing the complete circuit.

Installation details that affect safety

Hazardous-area wiring, cable selection and initial inspection should follow the applicable requirements, including IEC 60079-14 where relevant. Cables need suitable current and voltage ratings, mechanical protection, operating-temperature suitability and compatibility with the glands used. For Zone 1 or Zone 2 gas installations, use certified Ex e cable glands, conduit entries or stopping plugs as appropriate. Dust installations require the corresponding certified Ex t components.

Earthing and screening also need deliberate treatment. The guide recommends avoiding multiple earthing points that could create circulating currents. Cable screens are commonly earthed or bonded in the safe area and isolated elsewhere; the indicator provides terminals to maintain screen continuity without earthing the screen at the instrument. Follow the site’s earthing design and installation drawings.

For GRP enclosures, the enclosure is made slightly conductive to reduce electrostatic-charge accumulation. If mounting does not provide a suitable discharge path, use the internal earth terminal. The same guidance applies to a stainless-steel enclosure where the mounting structure does not provide a secure earth.

Using the indicators in combustible dust areas

The described indicators also have Ex tb protection by enclosure. Their dust protection combines an approved enclosure with the encapsulated assembly’s limitation of power dissipation, which defines the enclosure’s maximum external surface temperature. The stated dust marking includes IIIC, T80°C and EPL Db, subject to the product’s certification and ambient-temperature range.

For the specified installation, the guide identifies minimum ignition temperatures of 120°C for a dust cloud and 155°C for a dust layer up to 5 mm thick. A thicker layer requires assessment using IEC 60079-14. Verify that the actual dust group, ignition characteristics, ambient conditions and other hazardous-area equipment are covered before selecting the instrument. Where gas and combustible dust may occur together, take a cautious approach and confirm that both hazards are adequately addressed.

Inspection and maintenance

Inspection should be planned under the applicable site procedures and IEC 60079-17. A visual inspection checks that the instrument is the intended model, is reasonably clean and undamaged, and has glands and adjacent cables in good condition. A more detailed inspection may be appropriate when there is reason to suspect damage or deterioration; unnecessary removal of covers and interference with the electronics should be avoided.

The guide does not call for routine maintenance. If the display window needs cleaning, use a damp cloth. If the instrument appears faulty, first confirm the condition from the safe area where practical. Do not break an energized circuit in a hazardous area to measure current. Isolate the circuit before disconnecting the indicator, and carry out work only under the site’s permitted procedures. Live maintenance of Ex eb and Ex tb apparatus is not permitted in Zones 1 and 21; work in Zones 2 and 22 requires a risk assessment demonstrating that it is acceptably safe.

Practical implications for specification

Ex eb indicators can simplify some hazardous-area display installations by combining increased safety, encapsulation and intrinsic safety within the instrument, while avoiding the barrier requirement associated with a conventional intrinsically safe arrangement. Safe selection still depends on matching certification to the gas or dust hazard, checking the complete loop voltage budget, using suitable glands and wiring, and following site-specific inspection and maintenance controls. Treat those checks as part of the instrument specification—not as steps to leave until commissioning.