An ATEX gas detection system must do more than identify a target gas: its equipment configuration, installation and safety function must also suit the hazardous area and the process risk. The S5000 fixed gas detection system combines a transmitter with compatible sensors and, where needed, remote junction boxes. Its EU-type examination certificate defines approved configurations and conditions that engineers and operators need to consider when specifying, installing and maintaining the equipment.

How the S5000 fixed gas detection system is configured

The transmitter is the system’s control unit. It contains associated circuitry, connection facilities and an LED display visible through the enclosure window. Depending on sensor selection, it can support one or two sensors, mounted at the transmitter or remotely through S5000 Junction Boxes. The certificate permits specified combinations rather than an unrestricted mix of components.

Approved arrangements include two Digital Sensors, one IR400 sensor paired with one Digital Sensor, or one Universal Gas passive-sintered sensor. Digital Sensors can be configured for combustible gases, toxic gases or oxygen; the IR400 is for combustible gas detection; and Universal Gas sensor heads are available for combustible gas or hydrogen sulfide detection. A Junction Box accommodates one sensor, and the coding of an attached sensor can limit the approval and operating conditions of the transmitter or junction box.

This makes model-code and certificate review part of system design. Sensor type, enclosure version and the intended hazardous-area classification all matter. The certificate lists different protection markings and ambient-temperature limits for different configurations, so a component’s rating should not be assumed to apply unchanged to the assembled system.

ATEX gas detection system protection and sensor choices

The transmitter and junction boxes use flameproof protection (Ex db) and protection by enclosure for dust (Ex tb). Their certified enclosure ratings include IP66. The Digital Sensor with FRIT—the sintered element in its housing—also uses Ex db and Ex tb protection, with an IP65 enclosure rating. These markings describe certified protection characteristics; they do not remove the need to follow the equipment’s installation conditions.

The sensor technologies serve different measurement needs:

  • Digital Sensors: use catalytic sensing elements for combustible-gas configurations or electrochemical elements for toxic-gas and oxygen detection. The module includes a pre-amplifier and digitizes the measurement for communication with the transmitter.
  • IR400: an infrared detector for combustible gases that communicates with the transmitter through a 4–20 mA loop.
  • Passive catalytic sensors: use a catalytic bead without additional electronics; signal amplification and processing take place in a dedicated transmitter board.
  • Passive MOS sensors: use a heated metal oxide semiconductor element for high-concentration hydrogen sulfide sensing, with signal processing handled by the transmitter.
  • Universal Gas sensor heads: passive-sintered options are specified for combustible gas or H2S detection.

The certificate identifies selected combustible-gas configurations as meeting EN 60079-29-1 requirements. That performance approval does not apply to every sensor option; the certificate specifically excludes some Universal Gas models from combustible-gas detection performance approval. Confirm the exact sensor model and intended use against the applicable certificate and product documentation.

What the safety-related function means for integration

For its defined safety function, the S5000 provides a host system with a predefined 4–20 mA alarm signal and can de-energize a relay, if one is fitted, when the configured sensor detects a dangerous or explosive atmosphere. The output current represents operating states such as ready, warning, alarm, fault, calibration, maintenance or over-range. Default values differ according to output settings, so control-system designers should use the product documentation when defining input interpretation and alarm logic.

Certification to EN 50271:2010 recognizes application in a safety-related loop, but it does not establish suitability for every process safety function by itself. The certificate requires competent personnel to select and configure the equipment, validate the overall arrangement, and perform maintenance and repair in line with manufacturer instructions. It also states that the safety-related device must function and be powered independently of control devices required for operation. Further assessment is required when combining the detector with specific equipment under control and before using it to control explosion risk.

Installation, maintenance and proof testing

Specific conditions of use are important to hazardous-area compliance and ongoing operation. The transmitter is designed for vertical field mounting, and permitted conduit-entry locations and orientation must follow the product manual. The Digital Sensor’s installation also has defined connection requirements: its ¾-inch NPT thread must connect to a suitably certified enclosure, with five fully engaged threads tightened wrench-tight. The sensor may only be fitted to enclosures within the certificate’s stated maximum reference pressure. If it is removed, the manufacturer must be contacted before reinstallation.

Other conditions apply across the equipment:

  • Clean the transmitter, junction box and Digital Sensor only with a damp cloth, because non-metallic enclosure parts may build an ignition-capable electrostatic charge in certain extreme circumstances.
  • Do not repair flameproof joints.
  • Follow the installation orientation in the operating manual to achieve the stated ingress protection rating.
  • Observe the manufacturer’s instructions for application, environmental conditions, operation, maintenance, proof testing, maximum ratings and repair.

For the S5000 safety function, the stated proof-test interval is three months. The functional safety analysis also uses a 2,190-hour proof-test interval and assumes a four-hour mean time to restoration. These values are part of the documented safety assessment, not a substitute for site-specific validation or the operating procedures required for the application.

Practical implications for plant teams

For engineers and system integrators, the central task is to specify the complete detector configuration—not simply select a transmitter or sensor in isolation. Check the gas target, sensor technology, model code, enclosure and protection marking, temperature range, wiring interface and any relay requirement against the hazardous-area classification and control-system design. For plant managers and operations teams, maintain the prescribed proof-test schedule and ensure that only competent personnel handle safety-function configuration, validation and repair.

The S5000 certificate provides a defined basis for using the system in specified hazardous-area applications, while making clear that configuration and installation determine the applicable limits. Applying those conditions carefully helps keep the gas detection system aligned with both hazardous-area requirements and its intended role in the plant’s safety architecture.