Solar collector optimization is an important part of designing thermally driven cooling systems. In a solar absorption system, the collector must deliver heat at a temperature suitable for the chiller, while operating efficiently under available conditions. Inlet water temperature and coolant flow rate affect both the collector’s useful heat output and its efficiency, so choosing operating conditions is more than a matter of maximizing outlet temperature.

Computational fluid dynamics (CFD) analysis of flat plate collectors (FPCs) and photovoltaic thermal (PVT) collectors examined these operating variables and optimized them for integration with absorption cooling. The results show different trade-offs for thermal-only and combined thermal-electrical collection, and demonstrate why collector performance should be considered in relation to the cooling system’s required driving temperature.

Why operating conditions matter in solar absorption cooling

An absorption chiller uses heat supplied to its generator to support the refrigeration cycle. In a solar-driven system, collectors capture solar energy and transfer it to a circulating fluid, which may pass through a storage tank before supplying the chiller. The collector therefore needs to provide heat at a usable temperature, not simply collect as much solar energy as possible.

Collector thermal efficiency generally declines as the fluid inlet temperature rises. A warmer inlet increases the temperature difference between the collector and its surroundings, which contributes to greater heat loss. Flow rate also matters: it affects how much heat the fluid carries away and the temperature rise it experiences while passing through the collector. These variables influence outlet temperature and useful energy together, so they need to be assessed against the operating requirements of the cooling system.

The study used CFD models for FPC and PVT collectors and validated them against experimental data reported in the literature. It then examined the impact of inlet temperature and flow rate, followed by multi-objective optimization of the collector operating conditions.

Flat plate collector optimization: balancing temperature and efficiency

Flat plate collectors are used to produce hot water and can be considered for single-effect absorption cooling. In the modeled FPC, raising the inlet water temperature from 298 K to 370 K reduced thermal efficiency by 30%. This illustrates a key design consideration: a high inlet temperature may be necessary for a particular application, but it can reduce the share of collected solar energy delivered as useful heat.

Increasing flow rate does not necessarily provide continuing performance gains. The analysis found no significant impact on FPC performance when the total flow rate exceeded 36.4 × 10-3 kg/s/m2. Once flow is above this level, further increases may have limited influence on the modeled thermal efficiency. That does not mean flow rate is unimportant; rather, it suggests that its effect should be evaluated over the relevant operating range instead of assuming that more flow always improves performance.

For the specified cooling-system conditions, the optimized FPC operating point was a mass flow rate of 0.0067 kg/s/m2 and an inlet temperature of 321 K. At this point, the modeled thermal efficiency was 84%. These values are specific to the study’s collector model and optimization conditions, not universal settings for every installation. In practice, the required delivery temperature and the characteristics of the collector and cooling system determine which operating point is appropriate.

PVT collectors add an electrical performance trade-off

A PVT collector combines photovoltaic electricity generation with thermal collection. This can provide two useful outputs, but the electrical side introduces another performance measure: photovoltaic cell temperature. The study found that increasing inlet water temperature from 273 K to 373 K reduced PVT thermal efficiency by 7%, while electrical efficiency fell by 45%. The reported electrical reduction was associated with the increase in photovoltaic layer temperature.

This contrast matters for system design. Evaluating a PVT collector only by its thermal output can overlook the effect of operating temperature on electricity generation. Likewise, focusing solely on electrical efficiency does not capture the heat supplied to the cooling system. Both outputs need to be considered when selecting inlet conditions for an application that uses PVT heat to drive cooling.

As with the FPC, the study found no significant performance impact when PVT flow rate exceeded a total of 35 × 10-3 kg/s/m2. Its multi-objective optimization identified a flow rate of 0.0165 kg/s/m2 and an inlet temperature of 337.36 K. At these conditions, modeled thermal efficiency was 81.32% and electrical efficiency was 11.26%. These are results for the modeled collector and specified optimization criteria; system designers should not treat them as guaranteed field performance.

Applying the findings to system design

The results offer a practical framework for evaluating collector operation as part of an integrated solar cooling system:

  • Start with the chiller requirement. Establish the driving temperature needed for the absorption cooling application before selecting collector conditions.
  • Assess inlet temperature and flow together. A suitable operating point depends on both the required outlet conditions and the collector’s thermal or electrical performance.
  • Look for diminishing returns. The reported flow-rate thresholds indicate that further increases beyond certain levels did not significantly affect performance in the modeled cases.
  • Account for PVT’s two outputs. Compare thermal and electrical efficiency together, particularly because higher photovoltaic layer temperatures affected electrical performance in the analysis.
  • Validate against the actual system. The optimized values are tied to the models and specified conditions studied. Collector design, ambient conditions, and the cooling system’s operating requirements should inform any application.

Optimization can also support the broader goal of improving solar coefficient of performance (SCOP), which relates cooling output to solar energy supplied. The study’s approach links collector inlet conditions to the temperature requirements of absorption cooling rather than treating collector efficiency as an isolated figure. It does not establish a single universal SCOP improvement; instead, it shows how operating conditions can be selected to support system-level performance.

Practical implications

For engineers and system integrators, the central lesson is that solar collector performance depends on the operating point as well as the collector type. Raising inlet temperature can reduce efficiency, and flow-rate increases may reach a point where additional change has little effect. PVT systems require an added check on photovoltaic temperature and electrical efficiency. By matching inlet conditions to the cooling system’s driving-temperature needs and evaluating all relevant outputs, designers can make more informed choices about integrating FPC or PVT collectors into solar absorption cooling applications.